Kyoritsu | K2200

Back to list

Kyoritsu

Slim multimeter clamp, 1000A AC, 600V AC/DC, diam.33mm

Code :
KYOK2200
Brand :
Kyoritsu
Manufacturer Ref. :
K2200
Order Ref. :
K2200
Ultra Slim and lightweight Handy design.
1000A AC Clamp Meter.
AC 40/400/1000A Auto Range.
Diam.33mm Tear Drop Jaw easy to use in tight places.
DMM function ACV, DCV, Resistance, Continuity Buzzer.
Fuseless electronic protection on up Ω/ to 600V
IEC61010-1 Safety Standard
CAT.III 600V (AC A)
CAT.III 300V / CAT.II 600V (AC/DC V)
Refer to a friend
Share |
Top
TRMS : No
Jaw opening : Diam. 33mm
Current : AC (Alternative)
Voltage : AC (Alternative)
DC (Continuous)
Min. DC voltage : 400mV DC (Range)
Min. AC voltage : 4V AC (Range)
Max. DC voltage : 600V DC
Max. AC voltage : 600V AC
Min. DC current : na
Min. AC current : 40A AC (Range)
Max. DC current : na
Max. AC current : 1000A AC
additonal measurements : Resistance
Continuity test
Bandwidth : nc
Autonomy : nc
Safety Level : CAT I
CAT II
CAT III
Safety Overvoltage : CAT III 600V (AC A)
CAT III 300V / CAT II 600V (AC/DC V)
Additional Characteristics : Slim clamp
Package includes : 2 R03 AAA batteries, test leads, carrying case, user manual
Dimension (HxWxD) (mm) : 190x68x20 mm
Jaw width: 10mm
Net Weight : 120 g
Standard Manufacturer Warranty : 3 YEARS
Top
Kyoritsu 2200

AC Digital Clamp Meter

 

Ultra Slim and lightweight Handy design
1000A AC Clamp Meter
AC40/400/1000A Auto Range
Φ33mm Tear Drop Jaw easy to use in tight places
DMM function ACV, DCV, Ω, Continuity Buzzer
Fuseless electronic protection on up Ω/ to 600V
IEC61010-1 Safety Standard
CAT.III 600V (AC A)
CAT.III 300V / CAT.II 600V (AC/DC V)

 
AC A
40.00/400.0/1000A (Auto-ranging)
±1.4%rdg±6dgt (50/60Hz)
±1.6%rdg±6dgt (45~65Hz)
AC V
4.000/40.00/400.0/600V (Auto-ranging)
±1.8%rdg±7dgt (45~65Hz)
±2.3%rdg±8dgt (65~500Hz)
DC V
400.0mV/4.000/40.00/400.0/600V (Auto-ranging)
±1.0%rdg±3dgt (*1)
Ω
400.0Ω/4.000/40.00/400.0kΩ/4.000/40.00MΩ (Auto-ranging)
±2.0%rdg±4dgt (0~400kΩ)
±4.0%rdg±4dgt (4MΩ)
±8.0%rdg±4dgt (40MΩ)
Continuity buzzer buzzer sounds below 50±30Ω
Conductor size Ø33mm max.
Withstand voltage 5320V AC for 5 seconds (AC A)
3540V AC for 5 seconds (AC/DC V)
Applicable standards IEC 61010-1
CAT.III 600V Pollution degree 2 (AC A),
CAT.III 300V / CAT.II 600V Pollution degree 2 (AC/DC V)

IEC 61010-031, IEC 61010-2-032, IEC 61326 (EMC)
Power source
R03/LR03 (AAA) (1.5V) × 2
* continuous measuring time:
approx. 350 hours (Auto power off: approx. 10 minutes)
Dimensions 190(L) × 68(W) × 20(D)mm
Weight Approx. 120g (including batteries)
Accessories 7107A (Test leads), 9160 (Carrying case), R03 (AAA) × 2,
Instruction Manual
Optional 8008 (Multi-Tran)
(*1)  400.0mV Range : Accuracy is not guaranteed.
var webleads_site_ids = webleads_site_ids || []; webleads_site_ids.push(100836642); (function() { var s = document.createElement('script'); s.type = 'text/javascript'; s.async = true; s.src = ( document.location.protocol == 'https:' ? 'https://stats.webleads-tracker.com/js' : 'http://stats.webleads-tracker.com/js' ); ( document.getElementsByTagName('head')[0] || document.getElementsByTagName('body')[0] ).appendChild( s ); })(); window.sendinblue=window.sendinblue||[];window.sendinblue.methods=["identify","init","group","track","page","trackLink"];window.sendinblue.factory=function(e){return function(){var t=Array.prototype.slice.call(arguments);t.unshift(e);window.sendinblue.push(t);return window.sendinblue}};for(var i=0;i var doofinder_script = '//cdn.doofinder.com/media/js/doofinder-4.latest.min.js'; (function(d,t){var f=d.createElement(t),s=d.getElementsByTagName(t)[0];f.async=1; f.src=('https:'==location.protocol?'https:':'http:')+doofinder_script; s.parentNode.insertBefore(f,s)}(document,'script') ); if(!doofinder){var doofinder={};} doofinder.options = { "lang": "fr", "dtop": 12, "zone": "eu1", "dleft": -14, "results": { "width": 600, "defaultTemplate": "GridView" }, "header": {}, "queryInput": "#term", "hashid": "7137ecc6ddb78a4f05857292358ddd8d" }; //-->