Presentation

Voltage & Frequency
Wiring polarity
Insulation Resistance (500, 1000 V)
Continuity
Loop & Line Resistance
PFC/PSC (short-circuit current)
RCD tripping time
Leads compensation
EN61557/VDE0413/NFC15-100 compliant
<< Similar products

Download the data sheet
|
| |
 |
| Monitorable by computer : | No
| | Method of Earth measurement (Type) : | Without rod
| | Insulation min (Ohm) : | 100 kOhm
| | Insulation max (Ohm) : | 1 GOhm
| | Test voltage (V) : | 500 V 1000 V
| | Voltage measure max (V) : | 500 V AC
| | Differential test (A) : | 10mA 30mA 100mA 300mA 500mA 1000mA
| | Autonomy (Hour) : | nc
| | Safety Level : | CAT I CAT II CAT III
| | Safety Overvoltage : | CAT III 500 V
| | Additional Characteristics : | Leads compensation.
Complies with EN61557/VDE 0413/NFC 15-100.
| | Package includes : | 6 AA Cell batteries, hard carrying case, large crocodile clips, mains test cord, test leads, test probes, padded carrying strap, quick reference guide, remote control probe and lead, user guide on CD-ROM
| | Dimension (HxWxD) (mm) : | 100x250x125 mm
| | Net Weight (kg) : | 1.17 kg
| | Standard Manufacturer Warranty (Year) : | 3 YEARS | |
|
| |
 |
Brand : Fluke Serie : 1650 Manufacturer Ref. : 1651 Order Ref. : FLUKE-1651-01 Weight : 3.17 kg
Fluke 1650 Series Multifunction Installation Testers
The 1650 Series testers
verify the safety of electrical installations in domestic, commercial
and industrial applications. They can ensure that fixed wiring is safe
and correctly installed to meet the requirements of IEC 60364, HD 384
and all relevant local standards. The unique ergonomic design, low
weight, and padded neck-strap to free your hands, make operating a
Fluke 1650 multifunction tester a pleasure. With easy-to-operate
controls and a large display with exceptionally wide viewing angle,
it's also comfortable and safe to use. Select from three models:
- Fluke 1651: Performs all basic installation tests including continuity/insulation/loop impedance and RCD tripping time
- Fluke 1652: Also provides RCD tripping current level and RCD auto-testing
- Fluke
1653: As Fluke 1652 but with earth resistance and phase sequence
measurement. Has internal memory and a PC interface for documentation
and reporting
| Specifications |
| AC Voltage Measurement |
| Range: |
500 V |
| Resolution: |
0.1 V |
| Accuracy (50 - 60 Hz) |
0.8% + 3 |
| Input Impedance |
3.3 MΩ |
| Overload Protection |
660 Vrms |
|
| Continuity Testing |
| Range (autoranging): |
20 Ω, 200 Ω, 2000 Ω |
| Resolution: |
0.01 Ω, 0.1 Ω, 1 Ω |
| Test Current: |
> 200 mA |
| Open Circuit Voltage: |
> 4 V |
| Accuracy: |
± (1.5%+3 digits) |
|
| Insulation Resistance Measurement |
| Fluke 1651 |
|
| Test Voltage: |
500 - 1000 V |
| Accuracy of Test Voltage:¹ |
+10% , -0% |
|
|
| Fluke 1652 |
|
| Test Voltage: |
250 - 500 - 1000 V |
| Accuracy of Test Voltage:¹ |
+10% , -0% |
|
|
| Fluke 1653 |
|
| Test Voltage: |
50 - 100 - 250 - 500 - 1000 V |
| Accuracy of Test Voltage:¹ |
+10% , -0% |
| ¹ |
at rated test current |
|
|
| Test Voltage: |
50 V |
| Test Current: |
1 mA @ 50 kΩ |
| Insulation: |
10 kΩ - 50 мΩ |
| Resolution Resistance Range: |
0.01 мΩ |
| Accuracy: |
± (3% + 3 digits) |
|
|
| Test Voltage: |
100 V |
| Test Current: |
1 mA @ 100 kΩ |
| Insulation: |
100 kΩ - 20 MΩ |
| Resolution Resistance Range: |
0.01 MΩ |
| Accuracy: |
± (3% + 3 digits) |
| Insulation: |
20 MΩ - 100 MΩ |
| Resolution Resistance Range: |
0.1 MΩ |
| Accuracy: |
± (3% + 3 digits) |
|
|
| Test Voltage: |
250 V |
| Test Current: |
1 mA @ 250 kΩ |
| Insulation: |
100 kΩ - 200 MΩ |
| Resolution Resistance Range: |
0.1 MΩ |
| Accuracy: |
± (1.5% + 3 digits) |
|
|
| Test Voltage: |
500 V |
| Test Current: |
1 mA @ 500 kΩ |
| Insulation: |
100 kΩ - 200 MΩ |
| Resolution Resistance Range: |
0.1 MΩ |
| Accuracy: |
± (1.5% + 3 digits) |
| Insulation: |
200 MΩ - 500 MΩ |
| Resolution Resistance Range: |
1 MΩ |
| Accuracy: |
10% |
|
|
| Test Voltage: |
1000 V |
| Test Current: |
1 mA @ 1 MΩ |
| Insulation: |
100 kΩ - 200 MΩ |
| Resolution Resistance Range: |
0.1 MΩ |
| Accuracy: |
± (1.5% + 3 digits) |
| Insulation: |
200 MΩ - 500 MΩ |
| Resolution Resistance Range: |
1 MΩ |
| Accuracy: |
10% |
|
|
| Auto Discharge: |
Discharge time constant, 0.5 second for C = 1 µF or less |
| Live Circuit Detection: |
Inhibits test if terminal voltage > 30 V prior to initiation of test |
| Maximum Capacitive Load: |
Operable with the 5 µF load |
|
| Loop Impedance Measurement |
| Range: |
100 - 500 VAC (50/60 Hz) |
| Input connection: |
Soft Key selection |
| Loop impedance: |
Phase to earth |
| Line impedance: |
Phase to neutral |
| Limit on consecutive tests: |
Automatic thermal shutdown after 50 consecutive tests at 10 second intervals (typical) |
|
|
| Range: |
20 Ω |
| Resolution: |
0.01 Ω |
| Accuracy: |
±(3% + 10 digits) |
| Range: |
200 Ω |
| Resolution: |
0.1 Ω |
| Accuracy: |
±(3% + 10 digits) |
| Range: |
2000 Ω |
| Resolution: |
1 Ω |
| Accuracy: |
±(3% + 10 digits) |
|
| PFC, PSC Test |
| Computation: |
PFC or PSC determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance |
| Range: |
0 - 25 kA |
| Resolution (Ik < 1000 A): |
1 A |
| Resolution (Ik >= 1000 A): |
0.1 kA |
| Accuracy: |
Determined by accuracy of loop resistance and mains voltage measurements. |
|
| RCD Testing |
| Fluke 1651 |
²AC, G, S |
| Fluke 1652 |
²AC, G, S, A |
| Fluke 1653 |
²AC, G, S, A |
|
| Tripping Time Test (?T) |
| Trip Time Accuracy |
±(1% Reading + 1 digit) |
|
|
| Multiplier: |
x ½ |
| Current Settings: |
10, 30, 100, 300, 500, 1000 mA |
| Current Accuracy: |
+0% - 10% |
| RCD Type: |
²G |
| Measurement Range (EU): |
310 ms |
| Measurement Range (UK): |
2000 ms |
| RCD Type: |
²S |
| Measurement Range (EU): |
510 ms |
| Measurement Range (UK): |
2000 ms |
|
|
| Multiplier |
x 1 |
| Current Settings: |
10, 30, 100, 300, 500, 1000 mA |
| Current Accuracy: |
+10% - 0% |
| RCD Type: |
²G |
| Measurement Range (EU): |
310 ms |
| Measurement Range (UK): |
310 ms |
| RCD Type: |
²S |
| Measurement Range (EU): |
510 ms |
| Measurement Range (UK): |
510 ms |
|
|
| Multiplier: |
x 5 |
| Current Settings: |
10, 30 mA |
| Current Accuracy: |
±10% |
| RCD Type: |
²G |
| Measurement Range (EU): |
50 ms |
| Measurement Range (UK): |
50 ms |
| RCD Type: |
²S |
| Measurement Range (EU): |
160 ms |
| Measurement Range (UK): |
160 ms |
|
| Tripping Current (ramp) Test - Fluke 1652, Fluke 1653 |
| Current Range: |
50% - 110% of RCD's rated current |
| Step Size: |
10% of IΔN |
| Dwell time (Type ²G): |
300 ms / step |
| Dwell time (Type ²S): |
500 ms / step |
| Trip Current Measurement Accuracy: |
±5% |
|
| Earth Resistance Test (RE) - Fluke 1653 |
| Range: |
200 Ω |
| Resolution: |
0.1 Ω |
| Accuracy: |
±(2% + 5 digits) |
| Range: |
2000 Ω |
| Resolution: |
1 Ω |
| Accuracy: |
±(3.5% + 10 digits) |
| Frequency: |
128 Hz |
| Compliance Voltage: |
+25 V |
|
| Phase Sequence Indication - Fluke 1653 |
| Icon: |
Icon Phase Sequence indicator is active |
| Display of Phase Sequence: |
|
|
Displays ‘1-2-3’ in digital display field for correct sequence. |
|
Displays ‘3-2-1’ for incorrect phase. |
|
Dashes in place of a number indicate a valid determination could not be made. |
|
| ² RCD Types |
| G |
General, no delay |
| S |
Time delay |
| A |
Responds to pulsed signal |
| AC |
Responds to AC |
|
| Environmental Specifications |
| Operating Temperature |
|
| Humidity (Without Condensation) |
| 10 to 30 °C: |
95% |
| 30 to 40 °C: |
75% |
|
| Safety Specifications |
| Safety Rating |
|
| Mechanical & General Specifications |
| Size |
| (L x W x H): |
10 x 25 x 12.5 cm |
|
| Weight |
|
| Batteries |
|
| Warranty |
|
| Battery type |
|
Alkaline supplied, usable with 1.2V NiCD or NiMH rechargeable batteries |
|
|