Testoon Price : 473 € Exc VAT Quantity :


Brand : Fluke
Manufacturer Ref. : 1621
Presentation

Earth/resistivity tester 2 pole and 3 pole.
Measurement range: 0.15 - 2k Ohm.
Data recorder.
Auto detection of parasite voltage.
Measurement frequency: 128 Hz.
<< Similar products

Download the data sheet
|
| |
 |
| Method of Earth measurement (Type) : | With rod
| | Measures : | Outvoltage
| | Min resistance measure (Ohm) : | 150 mOhm
| | Max resistance measure (Ohm) : | 2 kOhm
| | Measure frequency (Hz) : | 128 Hz
| | Measure (Type) : | Earth Resistivity
| | Safety Level : | CAT I CAT II
| | Safety Overvoltage : | CAT II 600V
| | Display : | LCD backlight
| | Additional Characteristics : | -
| | Package includes : | One users manual, two measuring leads 2m with alligator clips, one 9V battery alkaline (LR61), one protective holster yellow, one CD-ROM
| | Dimension (HxWxD) (mm) : | 216x113x54 mm
| | Net Weight (kg) : | 850 g
| | Standard Manufacturer Warranty (Year) : | 1 YEAR | |
|
| |
 |
Brand : Fluke Manufacturer Ref. : 1621 Order Ref. : Fluke 1621 Weight : 1.2 kg
Fluke 1621
| General specifications |
| Measuring functions |
|
3-pole earth ground resistance, 2-pole ac resistance of a conductor,
Interference voltage |
|
| Intrinsic error |
|
Refers to the reference temperature range and is guaranteed for one year |
|
| Measuring rate |
|
| Battery[1] |
|
One 9 volt alkaline (LR61) |
|
| Battery condition |
|
LO-BAT is displayed if voltage drops below 6.5 V |
|
| Voltages |
| Between jacks H/C2 and E/C1: |
250 Veff maximum (effective voltage) |
| Between jacks S/P2 and E/C1: |
250 Veff maximum |
|
| Climatic class |
|
VDE/VDI 3540 RZ (conforming to KWG as per DIN 40040, 4/87) |
|
| Temperature performance[2] |
| Working: |
-10 °C to +50 °C (+14 °F to +122 °F) |
| Operating: |
0 °C to +35 °C (+32 °F to +95 °F) |
| Storage: |
-20 °C to +60 °C (+68 °F to +140 °F) |
| Reference: |
+23 °C ± 2 °C (+73 °F ± 4 °F) |
|
| Temperature coefficient |
|
± 0.1 % of range per degree Kelvin |
|
| Safety |
|
IEC/EN 61010-1, 600 V CAT II, pollution degree 2 |
|
| Dimensions |
|
113 mm x 54 mm x 216 mm (4.5 in x 2.1 in x 8.5 in), including holster |
|
| Weight |
|
850 g (1.9 lb), including standard accessories, volume approximately 600 cm3 |
|
| Note: |
|
[1]If the tester is not going to be used, or
is being stored for a long period, remove the battery and store
separately from the tester to avoid
damage from battery leakage. |
|
| Note: |
|
[2]The four temperature ranges for the tester
exists to satisfy European Standards requirements; the instrument can
be used over the full
working temperature range by using the temperature coefficient to
calculate accuracy at the ambient temperature of use. |
|
| Electrical specifications |
| Maximum deviations: |
| E1 Influence factor |
Position |
| E1 Deviation influence |
0 % |
| E2 Influence factor |
Supply voltage |
| E2 Deviation influence |
0 % |
| E3 Influence factor |
Temperature E3 |
| E3 Deviation influence |
2.3 % |
| E4 Influence factor |
Serial interference voltage (20 V) |
| E4 Deviation influence |
0.6 % |
| E5 Influence factor |
Probe- and auxiliary probe resistance |
| E5 Deviation influence |
10 % |
|
| Test voltage |
|
| Protection type |
|
| Electromagnetic compatibility |
|
Emission: IEC/EN 61326 Class B |
|
Immunity: IEC/EN 61326 Annex C |
|
| RE resistance measurement |
| Measuring method |
Current-voltage measurement with improved cross-talk attenuation,
no compensation of measuring lead resistance, with probe (3-pole)
or without probe (2-pole), as per IEC/EN 61557-5 |
| Open circuit voltage |
23 to 24 V ac |
| Short circuit current |
> 50 mA ac |
| Measuring frequency |
128 Hz |
| Maximum permissible
overload |
250 Veff |
|
| Measuring time |
|
8 seconds (average from when START is pressed) |
|
| Limit input |
|
Tester retains set value even if instrument is turned off (assuming
battery power supply is sufficient) |
|
| Automatic changeover of resolution |
| RH |
< 7 kΩ |
| Resolution |
0.01 Ω |
| RH |
< 50 kΩ |
| Resolution |
0.1 Ω |
| RH |
> 50 kΩ |
| Resolution |
1 Ω |
|
| Interference voltage display dc + ac |
| Vmax |
30 Veff |
| Common mode rejection |
> 80 dB at 50 Hz and
60 Hz |
| Ri |
680 kΩ |
| Measuring uncertainty |
< 10 % for pure ac
and dc signals |
|
| Measuring
range |
| 0.15 Ω to 20 Ω |
| Resolution |
0.01 Ω |
| Display range |
0 to 19.99 Ω |
|
| 200 Ω |
| Resolution |
0.1 Ω |
| Display range |
20 to 199.9 Ω |
|
| 2 kΩ |
| Resolution |
1 Ω |
| Display range |
200 to 1999 Ω |
|
| Intrinsic uncertainty |
|
± (6 % of
measured value
+ 5D) |
|
| Operating uncertainty IEC 61557[1] |
|
± (18 % of measured value + 5D) |
|
| Notes: |
|
[1] Covers all deviations caused by influence quantities E1-E5.
If the deviation E4 caused by high probe or auxiliary probe resistance is higher than specified flashes.
Measured values are outside of the specified operating uncertainty. |
|
|