<< Return

|
 |
Testoon Price : 599,40 € Exc VAT Quantity :


Brand : Kyoritsu
Manufacturer Ref. : K3022
Presentation

Digital Insulation and continuity tester.
• 3 functions in one unit, insulation test with 4 voltage ranges, continuity test, AC voltage measurement
• 200mA measuring current on continuity testing
• Comparator function with PASS / FAIL and buzzer
• 0Ohm adjustment at continuity measuring range
• Memory function up to 99 data
• Backlight LCD provides easy reading in dark locations
• Safety lock system prevents an erroneous operation on 500 and 1000 Volt ranges
• Safety standard IEC 61010-01 CAT.III 600V
<< Similar products

Download the data sheet
|
| |
 |
| Insulation min (Ohm) : | 100 kOhm
| | Insulation max (Ohm) : | 2 GOhm
| | Test voltage (V) : | 50 V 100 V 250 V 500 V
| | Voltage measure max (V) : | 720V
| | Continuity (Ohm) : | 400 Ohm
| | Leads compensation (Y/N) : | No
| | Autonomy (Hour) : | -
| | Safety Level : | CAT III
| | Safety Overvoltage : | CAT III 600V
| | Display : | Analog/Digital
| | Additional Characteristics : | Memory up to 99 data
| | Package includes : | Test lead with remote control switch, safety crocodile clip, test bar, extension prod, cord case, shoulder strap, R6P(AA)×6,
instruction manual
| | Dimension (HxWxD) (mm) : | 105x158x70 mm
| | Net Weight (kg) : | 500 g
| | Standard Manufacturer Warranty (Year) : | 3 YEARS | |
|
| |
 |
Brand : Kyoritsu Manufacturer Ref. : K3022 Order Ref. : 20060358 Weight : 0.8 kg
Kyoritsu K3022
| • |
3 functions in one unit, insulation test with 4 voltage ranges, continuity test, AC voltage measurement |
| • |
200mA measuring current on continuity testing |
| • |
Comparator function with PASS / FAIL and buzzer |
| • |
0Ω adjustment at continuity measuring range |
| • |
Memory function up to 99 data |
| • |
Backlight LCD provides easy reading in dark locations |
| • |
Safety lock system prevents an erroneous operation on 500 and 1000 Volt ranges |
| • |
Safety standard IEC 61010-01 CAT.III 600V |
Comparator Function
Select and set the standard resisitance value in each measuring range, and compare it with readings.
Notice the result of comparison by the or sign on the display, and by buzzer sound in same time.
Buzzer can be set either for or at your choice.

|
|
| |
| Insulation resistance |
| Test voltage |
50V |
100V |
250V |
500V |
Measuring range
(Auto range) |
4.000/40.00/200.0MΩ |
4.000/40.00/400.0/2000MΩ |
| First Effective Measuring range |
0.1~20MΩ |
0.1~40MΩ |
0.1~200MΩ |
| Mid-scale value |
5MΩ |
50MΩ |
| Accuracy |
|±(2%rdg+6dgt) |
| Second effective measuring range lower |
0~0.099MΩ |
| Second effective measuring range upper |
20.01~
200.0MΩ |
40.01~
2000MΩ |
200.1~
2000MΩ |
| Accuracy |
|±(5%rdg+6dgt) |
| Rated current |
DC 1~1.2mA |
| Output short circuit current |
1.5mA max |
| Ω/Continuity |
| Auto range |
40.00/400.0Ω |
| Accuracy |
|±(2%rdg+8dgt) |
| Output Voltage on open circuit |
5V±20% |
| Output short circuit current |
DC 220±20mA |
| Fuse |
Quick acting ceramic fuse 0.5A/600V(Ø6.35×32mm) |
| AC Voltage |
| Range |
AC 20~600V(50/60Hz)
DC -20~-600V/+20~+600V |
| Accuracy |
|±(3%rdg+6dgt) |
| General |
| Other function |
Data hold, Zero Ω ADJ., Auto discharge, Bar graph display, Memory, Comparator, Live circuit warning, Auto power off,
Battery alarm, Backlight, Safety lock, Remote measurement,
Measurement button lock(Continuous measurement) |
| Safety standard |
IEC/EN 61010-1 : 2001 CAT.III 600V IEC/EN 61557-1,2,4 |
| EMC standard |
IEC/EN 61326-1 (CE marking) |
| IP rating |
IP40 |
| Dimensions / Weight |
105(L) × 158(W) × 70(D)mm / 600g approx. |
| Power source |
R6P×6 or LR6×6 |
| Accessories |
7103(Test lead with remote control switch),
7131(Safety crocodile clip), 7161(Test bar), 8017(Extension prod),
9120(Cord case), 9121(Shoulder strap), R6P(AA)×6,
Instruction Manual |
| Optional |
7115(Extension Probe), 8016(Pickel Type Prod),
9089(Carrying Case) |
|
|
|
|
|
|